275 kV circuit breaker replacement planned by Moyle Interconnector Limited
- Moyle Interconnector Limited
- Northern Ireland
- 1 January 2028 to 31 December 2032
Moyle Interconnector Limited plans to replace the 275 kV circuit breakers on its 500MW link between Northern Ireland and Scotland. The 17 breakers sit at two converter stations and are nearing refurbishment.
The first phase covers four converter pole breakers, two at each station, during the summer outages planned for 2028 and 2029. Up to 13 more filter, transmission line and busbar coupler breakers may follow. The supplier would take the work from design to commissioning and add Point-on-Wave switching for the converter transformers.
Studies found a more demanding transient recovery voltage duty, tied to the low short-circuit ratio on the Scottish grid side. That may call for interrupters in a higher voltage class. Suppliers would have to prove compliance with test evidence and calculations. The final scope and structure will follow from this market engagement.
Due in 12 days· 4 Dec 2026
- What
- HV and LV distribution, switchgear and substations
- Estimated value
- Not published
- How it will be bought
- Not published
- Responses due
- 4 Dec 2026
- Contract dates
- Jan 2028 to Dec 2032