Four complete 210 kVA, 400 V UPS systems with 4 x 60 kW power modules and N+1 redundancy across Stoneleigh, Canley Brook and Burton Green sites. Includes VRLA battery systems for 90 minutes autonomy, 250 kVA isolation transformers, 400 A ATS and static switching, BMS monitoring interfaces, and FAT, SAT and resistive load bank testing. Canley Brook design load is TBC and site equipment quantities are to be confirmed before manufacture.